SafeTrace DLS

Features

  • 5°C to 54°C
  • 10 mm & 3/8"
  • Copper and stainless steel
Request a quote Give us a call or send an email phonelink_ring +31 (0)183-201088 forward_to_inbox sales@tc-e.nl

Application

Thermon SafeTrace DLS-IT is a metallic tracer tube covered with composite materials that lower thermal conductance to reduce heat transfer. SafeTrace provides a predictable heat output along a traced pipe to prevent hot spots and overheating. It replaces bare metallic tracers that often waste energy and stress pipe works by raising pipe temperatures much higher than desired.

SafeTrace DLS-IT tracers utilize a safety yellow identification jacket to signify materials potentially dangerous, such as steam per ASME/ANSI A13.1. All SafeTrace IT tracers also comply with ASTM Std C-1055, which requires that human skin temperature be less than 58°C (136.4°F) when in contact with a hot surface for five seconds.

SafeTrace DLS-IT is supplied in long length coils and may be run continuously from the steam supply manifold, along the pipe and over to the condensate return manifold.

Features

  • Significantly reduces risk of burns
  • Saves up to 50% of steam consumption compared to bare metal tube
  • Predictable heat transfer—no hot spots or overheating
  • Faster installation times—can be run continuously from the steam supply to the condensate collection system
  • Longer circuit lengths—fewer steam traps
  • Simple tape-on installation—not steel banding
  • Quick delivery
  • Free design assistance with Thermon CompuTrace-ST design software
SafeTrace DLS product configurations
SKU P/N Item Tube material Tube (O.D.) Wall thickness
TMN.C02.011 591022 DLS-IT-3B32 Copper 3/8" 0.032"
N/A N/A DLS-IT-3A35 SS welded 3/8" 0.035"
TMN.C02.012 59205 DLS-IT-3F35 SS seamless 3/8" 0.035"
TMN.C02.010 59275 DLS-IT-10B1 Copper 10 mm 1 mm
N/A N/A DLS-IT-10A1 SS welded 10 mm 1 mm
N/A N/A DLS-IT-10F1 SS seamless 10 mm 1 mm

Specifications

General

Manufacturer
Thermon
Unit of measurement
Meter

Specifications

Available tube diameters
10 mm and 3/8"
Nominal O.D.
25 mm (1")
Available tube materials
Copper & stainless steel
Typical pipe temperature range
5°C to 54°C
Maximum exposure temperature
215°C
Minimum installation temperature
-40°C
Maximum recommended steam pressure
17 bar
Typical maximum jacket temperature
<58°C
SafeTrace DLS

Request a quote

SafeTrace DLS

ring_volume +31 (0)183-201088 mail sales@tc-e.nl