T-75

Features

  • Tmax exposure 425°C
  • 114-227 W/m² • °C
  • 7.58 liter
Request a quote Give us a call or send an email phonelink_ring +31 (0)183-201088 forward_to_inbox sales@tc-e.nl

Application

Thermon T-75 is a heat transfer compound specifically formulated for its smooth texture and exceptional bonding strength. The smooth texture allows for easy spreading over surface heaters such as Thermon HeetSheet tank heating units and other plate type coils for applications above the temperature limits of Non-Hardening compounds 190°C. The compound may also be applied to steam or thermal fluid tracers that are attached to process piping and equipment for the purpose of heating or cooling. T-75 provides a highly efficient heat transfer for any surface mounted heater within its temperature range. In addition to tubular tracers, T-75 may also be applied to the surface of clamp-on heating elements or over small-bore rigid pipe tracers.

T-75 has superior surface wetting characteristics for excellent heat transfer rates where a good thermal bond is required. Contact resistance at the interface of the compound and the surface to be heated will diminish the heat transfer rate. Resistance to heat transfer is compounded due to scale, rust, grease or other contaminants that have not been removed from the contact surface before applying the heat transfer compound. Contact surfaces must be prepared just as though a paint or primer is to be applied. Surface pretreatment should be carried out in accordance with the appropriate SSPC (The Society for Protective Coatings) and NACE International (The Corrosion Society) surface preparation guides and specifications. Steam or thermal fluid tracers properly installed with T-75 will have a heat transfer coefficient of 114-227 W/m²-°C.

T-75 heat transfer compounds are supplied in rugged re-sealable pails and have a standard shelf life of 1 year prior to opening. Compounds will harden when exposed to air and heat.

T-75 may be applied by hand trowelling onto surfaces or may be installed with TFK channels for tracing applications.

For surface applications, T-75 is typically installed in layers of 1.5 mm to 6 mm thick. A 3.79-liter pail covers 1.10 m² of surface area with 3.0mm of material.

Features

  • Exceptional bond strength and resists thermal expansion and contraction
  • High shock resistance when exposed to extensive thermal cycling
  • Thermally stable at continuous temperature exposures at 425°C
  • Fine grain size and smooth texture for ease in workability
  • Water soluble for easy clean-up
T-75 product variants
SKU P/N Item Volume
TMN.C02.004 16061 T-75-2 7.58 liter

Specifications

General

Manufacturer
Thermon

Specifications

Container sizes
7.58 liter
Maximum continous exposure temperature
425°C
Minimum exposure temperature
-196°C
Minimum installation temperature
0°C
Heat transfer coefficient Ut (tracer to pipe wall)
114-227170 w/m²•°C
Shelf life (unopened)
12 months
Nominal bond shear
15.8 kg/cm²
Water-soluble