Application
Termon TEK series resistance constant wattage heating cables are used for long line temperature maintenance up to 101°C or freeze protection where circuit lengths exceed the limitations of parallel resistance heating cables. Circuit lengths up to 3658 meters can be energized from a single power supply point. The series circuitry of TEK provides consistent power output along the entire length of the cable without the voltage drop concerns associated with parallel tracer constructions.
TEK cables are approved for use in ordinary (nonclassified) and hazardous (classified) areas.
Features
- Pipe freeze protection and temperature maintenance up to 101°C
- Maximum exposure temperature of 232°C
- Circuit lengths of up to 3658 meters
- Rated up to 600 Vac
- Metallic braid for grounding purposes
- Fluoropolymer (FOJ) overjacket
- Available with 2 or 3 conductors
- Worldwide approvals
SKU | P/N | Item | Conductors | Resistance per conductor @ 20°C | Conductor size | Overjacket |
---|---|---|---|---|---|---|
N/A | N/A | TEK 2C40 | 2 | 0.01492 Ω/m | 16 AWG | Fluoropolymer |
N/A | N/A | TEK 2C50 | 2 | 0.009449 Ω/m | 14 AWG | Fluoropolymer |
N/A | N/A | TEK 2C60 | 2 | 0.005945 Ω/m | 12 AWG | Fluoropolymer |
N/A | N/A | TEK 2C70 | 2 | 0.003478 Ω/m | 10 AWG | Fluoropolymer |
TMN.A04.001 | 21209 | TEK 3C40 | 3 | 0.01492 Ω/m | 16 AWG | Fluoropolymer |
TMN.A04.002 | 21219 | TEK 3C50 | 3 | 0.009449 Ω/m | 14 AWG | Fluoropolymer |
TMN.A04.003 | 21227 | TEK 3C60 | 3 | 0.005945 Ω/m | 12 AWG | Fluoropolymer |
TMN.A04.004 | 20989 | TEK 3C70 | 3 | 0.003478 Ω/m | 10 AWG | Fluoropolymer |
Resources
Datasheet
English (Europe) datasheet
English (Americas) datasheet
Installation manual
English (Europe) installation instructions
English (Americas) installation instructions
Certifications/Approvals
FM Approvals
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups F and G
Class III, Divisions 1 and 2
Class I, Zones 1 and 2, AEx e II
Underwriters Laboratories Inc.
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups F and G
Class III, Divisions 1 and 2
Canadian Standards Association
Ordinary Locations
Class I, Division 2, Groups A, B, C and D
Ex e II
Specifications
General
- Manufacturer
- Thermon
- Unit of measurement
- Meter
Ratings
- Rated voltage
- Up to 600 Vac
- Maximum maintain temperature
- 101°C
- Maximum continuous exposure temperature
- Power-off 232°C
- Minimum installation temperature
- -51°C
- Minimum bend radius (metric)
- -15°C = 22 mm | -60°C = 32 mm