RSX

Features

  • 48 W/m @ 10°C
  • Tmax maintain 65°C
  • 208-240 Vac
Request a quote Give us a call or send an email phonelink_ring +31 (0)183-201088 forward_to_inbox sales@tc-e.nl

Application

Thermon RSX self-regulating heating cables are designed for freeze protection or process temperature maintenance applications up to 65°C, where the watt density requirements preclude the use of the standard range of BSX cables. These characteristics make RSX extremely suitable for application in grease-line flow maintenance systems which maintain the pipe temperature at 40°C in order to prevent greasy waste water from clogging the pipework due to the grease mixure cooling down and solidifying.

The heat output of the RSX cables varies in response to the surrounding conditions along the entire length of a circuit. Whenever the heat loss of the insulated pipe, tank or equipment increases (as ambient temperature drops), the heat output of the cable increases. Conversely, when the heat loss decreases (as the ambient temperature rises or product flows), the cable reacts by reducing its heat output. RSX heat tracing cables are available with polyolefin (OJ) overjacket suitable for mild inorganic solutions and with a fluoropolymer (FOJ) overjacket for higher chemical resistance against aggressive organics and corrosives.

RSX 15 heat trace cables are approved for use in ordinary (nonclassified) areas, hazardous (classified) areas, and Zone 1 and 2 classified areas.

Features

  • Pipe freeze protection and temperature maintenance up to 65°C
  • Safe and efficient in operation, uniform pipe temperatures and energy saving technology
  • Semiconductive self-regulating heating matrix allows for overlaps without overheating
  • Suitable for use in commercial kitchen grease-line flow maintenance systems
  • Cut-to-length parallel circuitry
  • Nickel-plated copper bus wires
  • Metallic braid for grounding purposes
  • Available with polyolefin (OJ) or fluoropolymer (FOJ) overjacket
  • Worldwide approvals
  • Meter markings on overjacket
  • Compatible with user-friendly and easy to install Thermon components
RSX product variants
SKU P/N Item Power output @ 10°C Voltage (Vac) Overjacket
TMN.A01.017 22662 RSX 15-2-OJ 48 W/m, 230 Vac 208-240 Polyolefin
TMN.A01.018 22663 RSX 15-2-FOJ 48 W/m, 230 Vac 208-240 Fluoropolymer

Certifications/Approvals

CE Ex
KEMA 07 ATEX0179 according to EU ATEX-directive 94/9/EC

IEC IECEx
KEM 07.0052

FM Approvals
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups B, C and D
Class II, Division 2, Groups F and G
Class III, Divisions 1 and 2
Class I, Zones 1 and 2, AEx e II (requires FOJ)

Underwriters Laboratories Inc.
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups F and G
Class III, Divisions 1 and 2

Canadian Standards Association
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 1, Groups A, B, C and D
Class II, Division 1, Groups E, F and G
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups E, F and G
Ex e II

Specifications

General

Manufacturer
Thermon
Unit of measurement
Meter

Ratings

Available watt densities at 230 Vac
48 W/m @ 10°C
Supply voltage
208-240 Vac
Maximum continuous exposure temperature
Power-on 65°C
Minimum installation temperature
-51°C
Minimum bend radius
-15°C = 10 mm | -60°C = 32 mm