Application
Thermon HTSX self-regulating trace heating cables are designed specifically for process temperature maintenance for temperatures up to 150°C or freeze protection where high temperature exposure capability is required. HTSX withstands the temperature exposures associated with steam purging. Constructed using Thermon’s unique and proven monolithic co-extrusion process, HTSX is the market leading self-regulating heat tracing technology.
The heat output of the HTSX cables varies in response to the surrounding conditions along the entire length of a circuit. Whenever the heat loss of the insulated pipe, tank or equipment increases (as ambient temperature drops), the heat output of the cable increases. Conversely, when the heat loss decreases (as the ambient temperature rises or product flows), the cable reacts by reducing its heat output. HTSX heat tracing cables are available with a fluoropolymer (FOJ) overjacket for higher chemical resistance against aggressive organics and corrosives.
The HTSX heat trace cables are approved for use in ordinary (nonclassified) areas and hazardous (classified) areas.
Features
- Pipe freeze protection and temperature maintenance up to 150°C
- Safe and efficient in operation, uniform pipe temperatures and energy saving technology
- Semiconductive self-regulating heating matrix allows for overlaps without overheating
- Cut-to-length parallel circuitry
- Nickel-plated copper bus wires
- Metallic braid for grounding purposes
- Available voltages 110-120, 208-277 and 380-480 Vac
- Worldwide approvals
- Meter markings on overjacket
- Compatible with user-friendly and easy to install Thermon components
SKU | P/N | Item | Power output @ 10°C | Voltage (Vac) | Tmax maintain | Overjacket |
---|---|---|---|---|---|---|
TMN.A01.025 | 24812 | HTSX 3-2-OJ | 9 W/m, 230 Vac | 208-277 | 150°C | Fluoropolymer |
TMN.A01.019 | 24802 | HTSX-3-1-OJ | 10 W/m, 120 Vac | 110-120 | 150°C | Fluoropolymer |
TMN.A01.026 | 24832 | HTSX 6-2-OJ | 18 W/m, 230 Vac | 208-277 | 150°C | Fluoropolymer |
TMN.A01.020 | 24822 | HTSX-6-1-OJ | 20 W/m, 120 Vac | 110-120 | 150°C | Fluoropolymer |
TMN.A01.027 | 24852 | HTSX 9-2-OJ | 28 W/m, 230 Vac | 208-277 | 150°C | Fluoropolymer |
TMN.A01.021 | 24842 | HTSX-9-1-OJ | 30 W/m, 120 Vac | 110-120 | 150°C | Fluoropolymer |
TMN.A01.031 | 24882 | HTSX 10-4-OJ | 33 W/m, 480 Vac | 380-480 | 121°C | Fluoropolymer |
TMN.A01.028 | 24872 | HTSX 12-2-OJ | 38 W/m, 230 Vac | 208-277 | 150°C | Fluoropolymer |
TMN.A01.022 | 24862 | HTSX-12-1-OJ | 39 W/m, 120 Vac | 110-120 | 150°C | Fluoropolymer |
TMN.A01.029 | 24952 | HTSX 15-2-OJ | 48 W/m, 230 Vac | 208-277 | 150°C | Fluoropolymer |
TMN.A01.023 | 24942 | HTSX-15-1-OJ | 49 W/m, 120 Vac | 110-120 | 150°C | Fluoropolymer |
TMN.A01.032 | 24982 | HTSX 15-4-OJ | 49 W/m, 480 Vac | 380-480 | 121°C | Fluoropolymer |
TMN.A01.030 | 24972 | HTSX 20-2-OJ | 64 W/m, 230 Vac | 208-277 | 150°C | Fluoropolymer |
TMN.A01.024 | 24962 | HTSX-20-1-OJ | 66 W/m, 120 Vac | 110-120 | 150°C | Fluoropolymer |
TMN.A01.033 | 24992 | HTSX 20-4-OJ | 66 W/m, 480 Vac | 380-480 | 121°C | Fluoropolymer |
Resources
Datasheet
English (Europe) datasheet
English (Americas) datasheet
Installation manual
English (Europe) installation instructions
English (Americas) installation instructions
Certifications/Approvals
CE Ex
FM12 ATEX 0014X according to EU ATEX-directive 94/9/EC
IEC IECEx
FMG 12.0004X
FM Approvals (120 and 240 Vac US only)
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups B, C and D
Class II, Division 2, Groups E, F and G
Class III
Canadian Standards Association
Ordinary Locations
Hazardous (Classified) Locations
Canada:
Class I, Division 1, Groups A, B, C and D
Class II, Division 1, Groups E, F and G
Class III
Ex 60079-30-1 IIC Gb
Ex 60079-30-1 IIIC Db
US:
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups E, F and G
Class III
Class I Zone 1 AEx 60079-30-1 IIC Gb
Class II Zone 21 AEx 60079-30-1 IIIC Db
Specifications
General
- Manufacturer
- Thermon
- Unit of measurement
- Meter
Ratings
- Available watt densities at 230 Vac
- 9, 18, 28, 38, 48, 64 W/m @ 10°C
- Available watt densities at 120 Vac
- 10, 20, 30, 39, 49, 66 W/m @ 10°C
- Available watt densities at 480 Vac
- 33, 49, 66 W/m @ 10°C
- Supply voltages
- 110-120, 208-277 or 380-480 Vac
- Maximum maintain temperature 110-277 Vac
- 150°C
- Maximum maintain temperature 380-480 Vac
- 121°C
- Maximum intermittent exposure temperature
- 250°C for 110-277 Vac
- Maximum intermittent exposure temperature
- 204°C for 380-480 Vac
- Maximum continuous exposure temperature
- Power-off 204°C
- Minimum installation temperature
- -60°C
- Minimum bend radius
- -15°C = 10 mm | -60°C = 32 mm