Features

  • 9 to 64 W/m @ 10°C
  • Tmax maintain 150°C
  • 110-120, 208-277 & 480 Vac
Request a quote Give us a call or send an email phonelink_ring +31 (0)183-201088 forward_to_inbox sales@tc-e.nl

Application

Thermon HTSX self-regulating trace heating cables are designed specifically for process temperature maintenance for temperatures up to 150°C or freeze protection where high temperature exposure capability is required. HTSX withstands the temperature exposures associated with steam purging. Constructed using Thermon’s unique and proven monolithic co-extrusion process, HTSX is the market leading self-regulating heat tracing technology.

The heat output of the HTSX cables varies in response to the surrounding conditions along the entire length of a circuit. Whenever the heat loss of the insulated pipe, tank or equipment increases (as ambient temperature drops), the heat output of the cable increases. Conversely, when the heat loss decreases (as the ambient temperature rises or product flows), the cable reacts by reducing its heat output. HTSX heat tracing cables are available with a fluoropolymer (FOJ) overjacket for higher chemical resistance against aggressive organics and corrosives.

The HTSX heat trace cables are approved for use in ordinary (nonclassified) areas and hazardous (classified) areas.

Features

  • Pipe freeze protection and temperature maintenance up to 150°C
  • Safe and efficient in operation, uniform pipe temperatures and energy saving technology
  • Semiconductive self-regulating heating matrix allows for overlaps without overheating
  • Cut-to-length parallel circuitry
  • Nickel-plated copper bus wires
  • Metallic braid for grounding purposes
  • Available voltages 110-120, 208-277 and 380-480 Vac
  • Worldwide approvals
  • Meter markings on overjacket
  • Compatible with user-friendly and easy to install Thermon components
HTSX product variants
SKU P/N Item Power output @ 10°C Voltage (Vac) Tmax maintain Overjacket
TMN.A01.025 24812 HTSX 3-2-OJ 9 W/m, 230 Vac 208-277 150°C Fluoropolymer
TMN.A01.019 24802 HTSX-3-1-OJ 10 W/m, 120 Vac 110-120 150°C Fluoropolymer
TMN.A01.026 24832 HTSX 6-2-OJ 18 W/m, 230 Vac 208-277 150°C Fluoropolymer
TMN.A01.020 24822 HTSX-6-1-OJ 20 W/m, 120 Vac 110-120 150°C Fluoropolymer
TMN.A01.027 24852 HTSX 9-2-OJ 28 W/m, 230 Vac 208-277 150°C Fluoropolymer
TMN.A01.021 24842 HTSX-9-1-OJ 30 W/m, 120 Vac 110-120 150°C Fluoropolymer
TMN.A01.031 24882 HTSX 10-4-OJ 33 W/m, 480 Vac 380-480 121°C Fluoropolymer
TMN.A01.028 24872 HTSX 12-2-OJ 38 W/m, 230 Vac 208-277 150°C Fluoropolymer
TMN.A01.022 24862 HTSX-12-1-OJ 39 W/m, 120 Vac 110-120 150°C Fluoropolymer
TMN.A01.029 24952 HTSX 15-2-OJ 48 W/m, 230 Vac 208-277 150°C Fluoropolymer
TMN.A01.023 24942 HTSX-15-1-OJ 49 W/m, 120 Vac 110-120 150°C Fluoropolymer
TMN.A01.032 24982 HTSX 15-4-OJ 49 W/m, 480 Vac 380-480 121°C Fluoropolymer
TMN.A01.030 24972 HTSX 20-2-OJ 64 W/m, 230 Vac 208-277 150°C Fluoropolymer
TMN.A01.024 24962 HTSX-20-1-OJ 66 W/m, 120 Vac 110-120 150°C Fluoropolymer
TMN.A01.033 24992 HTSX 20-4-OJ 66 W/m, 480 Vac 380-480 121°C Fluoropolymer

Certifications/Approvals

CE Ex
FM12 ATEX 0014X according to EU ATEX-directive 94/9/EC

IEC IECEx
FMG 12.0004X

FM Approvals (120 and 240 Vac US only)
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups B, C and D
Class II, Division 2, Groups E, F and G
Class III

Canadian Standards Association
Ordinary Locations
Hazardous (Classified) Locations

Canada:
Class I, Division 1, Groups A, B, C and D
Class II, Division 1, Groups E, F and G
Class III
Ex 60079-30-1 IIC Gb
Ex 60079-30-1 IIIC Db

US:
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups E, F and G
Class III
Class I Zone 1 AEx 60079-30-1 IIC Gb
Class II Zone 21 AEx 60079-30-1 IIIC Db

Specifications

General

Manufacturer
Thermon
Unit of measurement
Meter

Ratings

Available watt densities at 230 Vac
9, 18, 28, 38, 48, 64 W/m @ 10°C
Available watt densities at 120 Vac
10, 20, 30, 39, 49, 66 W/m @ 10°C
Available watt densities at 480 Vac
33, 49, 66 W/m @ 10°C
Supply voltages
110-120, 208-277 or 380-480 Vac
Maximum maintain temperature 110-277 Vac
150°C
Maximum maintain temperature 380-480 Vac
121°C
Maximum intermittent exposure temperature
250°C for 110-277 Vac
Maximum intermittent exposure temperature
204°C for 380-480 Vac
Maximum continuous exposure temperature
Power-off 204°C
Minimum installation temperature
-60°C
Minimum bend radius
-15°C = 10 mm | -60°C = 32 mm