Application
Thermon WarmTrace HSX self-regulating trace heating cables are specifically designed to maintain hot water supply piping at desired nominal maintenance temperatures. With 1.9 mm² bus wires (larger than any other system available), HSX can reduce the number of circuits required to install an electric heat traced system.
EASY TO DESIGN
A WarmTrace system replaces the complex recirculation network of return pipes, circulating pumps and balancing valves. For each hot water supply line, simply match the hot water maintenance temperature with the corresponding color-coded trace heater and insulate per the design guide. HSX self-regulating heat trace automatically maintains desired water temperatures. Changes in pipe diameters, flow rates and use patterns will not affect the design. Even variations in ambient or water temperature are compensated for as the trace heater adjusts its heat output along the entire length of a heat-traced pipe.
EASY TO INSTALL
HSX heat tracing is cut to length and installed directly on the supply piping under conventional thermal insulation with ordinary hand tools. Kits for power connection, end termination and splicing, plus other accessories, are designed for quick and easy installation. Increased circuit lengths with HSX mean less circuits to fabricate and fewer total circuits.
ECONOMICAL TO OPERATE AND MAINTAIN
A WarmTrace system replaces recirculation and eliminates the costs of continuously operating pumps, deliberately overheating the water and maintaining a recirculation system. Potential water savings can also be realized since the heat tracing can be installed up to the point of use—no waiting for hot water!
COMPONENTS
Thermon offers system accessories designed specifically for rapid, trouble-free installation of Thermon heat tracing. All trace heaters require a connection kit to comply with approval requirements. Information on accessories to complete a heater circuit installation can be found in the WarmTrace Systems Accessories product specification sheet.
Features
- Nominal maintain temperatures up to 60°C
- Safe and efficient in operation, uniform pipe temperatures and energy saving technology
- Semiconductive self-regulating heating matrix allows for overlaps without overheating
- Saves water and energy
- Simplified design and installation
- Cut-to-length parallel circuitry
- Nickel-plated copper bus wires
- Metallic braid for grounding purposes
- Hot water temperatures can be maintained without the need for thermostats
SKU | P/N | Item | Outer jacket color | Voltage (Vac) | Tnom maintain | Ambient range | Overjacket |
---|---|---|---|---|---|---|---|
TMN.A10.007 | 22530 | HSX 2105-2 | Blue | 208-277 | 41°C | 24-27°C | Polyolefin |
TMN.A10.008 | 22550 | HSX 2120-2 | Green | 208-277 | 49°C | 22-27°C | Polyolefin |
TMN.A10.009 | 22570 | HSX 2140-2 | Red | 208-277 | 60°C | 22-27°C | Polyolefin |
Resources
Datasheet
English (Europe) datasheet
English (Americas) datasheet
Installation manual
English (Europe) installation instructions
English (Americas) installation instructions
Certifications/Approvals
Underwriters Laboratories Inc. (UL Listed)
Canadian Standards Association
Specifications
General
- Manufacturer
- Thermon
- Unit of measurement
- Meter
Ratings
- Supply voltages
- 208-277 Vac
- Maximum nominal maintain temperature
- 60°C for HSX 2140
- Minimum bend radius (metric)
- -15°C = 10 mm | -60°C = 32 mm