HPT

Features

  • 15, 30, 46 & 61 W/m @ 10°C
  • Tmax maintain 210°C
  • 110-120, 208-277 & 480 Vac
Request a quote Give us a call or send an email phonelink_ring +31 (0)183-201088 forward_to_inbox sales@tc-e.nl

Application

Thermon high performance HPT power-limiting heating cables are designed specifically for process temperature maintenance up to 210°C and freeze protection where high maintain temperatures or high temperature exposure is required. HPT heating cables can be installed on piping, tanks, vessels and equipment. When powered off these cables can withstand continuous exposure temperatures of up to 260°C. All HPT heating cables have a fluoropolymer (FOJ) overjacket which provides high chemical resistance against aggressive organics and corrosives.

A coiled resistor alloy heating element provides the powerlimiting feature of HPT. This PTC (Positive Temperature Coefficient) characteristic decreases the cable’s power output as the heat-traced product temperature increases and allows the cable to be overlapped during installation. The composite construction of the heating element and fiber substrate, plus an additional fiber cushion layer, provide an exceptionally durable high performance heating cable.

HPT cables are approved for use in ordinary (nonclassified) areas, hazardous (classified) areas, and Zone 1 and 2 classified areas.

Features

  • Pipe freeze protection and temperature maintenance up to 210°C
  • Maximum exposure temperature of 260°C
  • PTC coiled resistive alloy heating element
  • Available service voltages 110 to 120, 208 to 277 and 480 Vac
  • Cut-to-length parallel circuitry
  • Nickel-plated copper bus wires
  • Metallic braid for grounding purposes
  • Fluoropolymer (FOJ) overjacket
  • Worldwide approvals
  • Compatible with user-friendly and easy to install Thermon components
HPT product variants
SKU P/N Item Power output @ 10°C Zone length Voltage (Vac) Tmax maintain Overjacket
TMN.A02.005 25812 HPT 5-2-OJ 15 W/m, 230 Vac 76 cm 208-277 210°C Fluoropolymer
TMN.A02.001 25802 HPT 5-1-OJ 16 W/m, 120 Vac 61 cm 110-120 210°C Fluoropolymer
TMN.A02.009 25402 HPT 5-4-OJ 16 W/m, 480 Vac 152 cm 480 210°C Fluoropolymer
TMN.A02.006 25832 HPT 10-2-OJ 30 W/m, 230 Vac 61 cm 208-277 190°C Fluoropolymer
TMN.A02.002 25822 HPT 10-1-OJ 33 W/m, 120 Vac 46 cm 110-120 190°C Fluoropolymer
TMN.A02.010 25412 HPT 10-4-OJ 33 W/m, 480 Vac 122 cm 480 190°C Fluoropolymer
TMN.A02.007 25852 HPT 15-2-OJ 46 W/m, 230 Vac 61 cm 208-277 175°C Fluoropolymer
TMN.A02.003 25842 HPT 15-1-OJ 49 W/m, 120 Vac 46 cm 110-120 175°C Fluoropolymer
TMN.A02.011 25422 HPT 15-4 OJ 49 W/m, 480 Vac 122 cm 480 175°C Fluoropolymer
TMN.A02.008 25872 HPT 20-2-OJ 61 W/m, 230 Vac 61 cm 208-277 150°C Fluoropolymer
TMN.A02.004 25862 HPT 20-1-OJ 66 W/m, 120 Vac 30 cm 110-120 150°C Fluoropolymer
TMN.A02.012 25432 HPT 20-4-OJ 66 W/m, 480 Vac 102 cm 480 150°C Fluoropolymer

Certifications/Approvals

CE Ex
FM13 ATEX 28 according to EU ATEX-directive 94/9/EC

IEC IECEx
FMG 06.0006

FM Approvals
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups B, C and D
Class II, Division 2, Groups F and G*
Class III, Divisions 1 and 2
Class I, Zones 1 and 2, AEx eb IIC; AEx tb IIIC

*CL. II, Div. 2 requires Thermon design review

Canadian Standards Association
Ordinary Locations
Hazardous (Classified) Locations
Class I, Divisions 1 and 2, Groups A, B, C and D
Class II, Divisions 1 and 2, Groups E, F and G
Ex eb IIC

Specifications

General

Manufacturer
Thermon
Unit of measurement
Meter

Ratings

Available watt densities at 230 Vac
15, 30, 46, 61 W/m @ 10°C
Available watt densities at 240 Vac
16, 33, 49, 66 W/m @ 10°C
Supply voltages
120, 240, 480, 575 Vac
Maximum maintain temperature
150°C to 210°C
Maximum continuous exposure temperature
Power-off 260°C
Minimum installation temperature
-51°C
Minimum bend radius
-15°C = 10 mm | -51°C = 32 mm
T-rating
T2 to T6 (based on stabilized design)