FP

Features

  • 8, 15, 24 & 33 W/m
  • Tmax maintain 65°C
  • 110-120, 208-277, 480 & 575 Vac
Request a quote Give us a call or send an email phonelink_ring +31 (0)183-201088 forward_to_inbox sales@tc-e.nl

Application

Thermon FP parallel resistance constant wattage heating cables are designed to provide freeze protection and process temperature maintenance for temperatures up to 65°C. FP heating cables can be installed on piping, tanks, vessels and equipment. When powered off these cables can withstand continuous exposure temperatures of up to 204°C. All FP cables have a fluoropolymer (FOJ) overjacket which provides high chemical resistance against aggressive organics and corrosives.

The parallel resistance configuration allows the cables to be cut to length and terminated in the field with easy-to-use Thermon kits. FP cables provide consistent and reliable heat outputs regardless of circuit length and are not subject to the inrush current (also known as startup current) associated with self-regulating heating cables. Therefore the need for over sizing power distribution equipment is eliminated.

FP cables are approved for use in ordinary (nonclassified) areas, hazardous (classified) areas and Zone 2 classified areas.

Features

  • Pipe freeze protection and temperature maintenance up to 65°C
  • Maximum exposure temperature of 204°C
  • Extended circuit lengths of up to 399 meters
  • Available service voltages 120, 240, 480 and 575 Vac
  • Cut-to-length parallel circuitry
  • Nichrome heating element
  • 4 mm² copper bus wires
  • Metallic braid for grounding purposes
  • Fluoropolymer (FOJ) overjacket
  • Worldwide approvals
  • Compatible with user-friendly and easy to install Thermon components
FP product variants
SKU P/N Item Power output Zone length Voltage (Vac) Overjacket
TMN.A03.002 22332 FP 2.5-2-OJ 8 W/m, 230 Vac 137 cm 230-240 Fluoropolymer
N/A N/A FP 2.5-1-OJ 8 W/m, 120 Vac 76 cm 120 Fluoropolymer
TMN.A03.003 22342 FP 5-2-OJ 15 W/m, 230 Vac 102 cm 230-240 Fluoropolymer
N/A N/A FP 5-1-OJ 16 W/m, 120 Vac 61 cm 120 Fluoropolymer
TMN.A03.001 22387 FP 8-2-OJ 24 W/m, 230 Vac 102 cm 230 Fluoropolymer
N/A N/A FP 8-4-OJ 18 W/m, 400 Vac 152 cm 400 Fluoropolymer
TMN.A03.004 22352 FP 10-2-OJ 33 W/m, 230 Vac 76 cm 230-240 Fluoropolymer
N/A N/A FP 10-1-OJ 33 W/m, 120 Vac 61 cm 120 Fluoropolymer
TMN.A03.005 22362 FP 10-4-OJ 33 W/m, 480 Vac 137 cm 480 Fluoropolymer
N/A N/A FP 10-5-OJ 33 W/m, 575 Vac 168 cm 575 Fluoropolymer

Certifications/Approvals

CE Ex
II 2 G Ex e II T3 to T6, II 2 D Ex tD A21 IP66/IP67
T200 °C to T85 °C FM 07ATEX0016

IEC IECEx
FMG 06.0008

FM Approvals
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups B, C and D
Class II, Division 2, Groups F and G
Class III, Divisions 1 and 2
Class I, Zones 1 and 2, AEx e II

Underwriters Laboratories Inc.
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups F and G
Class III, Divisions 1 and 2

Canadian Standards Association
Ordinary Locations
Hazardous (Classified) Locations
Class I, Divisions 1 & 2, Groups A, B, C and D
Class II, Divisions 1 & 2, Groups E, F and G
Ex e II

Specifications

General

Manufacturer
Thermon
Unit of measurement
Meter

Ratings

Available watt densities at 230 Vac
8, 15, 24, 33 W/m
Supply voltages
120, 240, 480, 575 Vac
Maximum maintain temperature
65°C
Maximum continuous exposure temperature
Power-off 204°C
Minimum installation temperature
-60°C
Minimum bend radius