TraceNet ECM-Ambient

Features

  • Ambient thermostat
  • Alarm relay + RS485
  • Single circuit or pilot control
Request a quote Give us a call or send an email phonelink_ring +31 (0)183-201088 forward_to_inbox sales@tc-e.nl

Application

The TraceNet ECM-Ambient thermostat line is designed to provide ambient sensing control of electric heat tracing circuits for freeze protection of piping and vessels. This thermostat can be used to control a heating circuit or as pilot control of a contactor switching multiple heat tracing circuits. ECM controllers can withstand a wide range of ambient temperatures where heat tracing for freeze protection or temperature maintenance is applied: from the Arctic -74°C to desert 55°C environments. The ECM-Ambient range provides energy savings and precise control for heat trace circuits.

The ECM-Ambient modules are housed in a glass reinforced nonmetallic Terminator wall mounted enclosure with an environmental protection IP66 rating. Rotary switches are provided for adjusting the temperature setpoint.

The standard versions of the ECM controllers can communicate on a RS485 physical network by using a Modbus RTU communication protocol. This also allows the controllers to be monitored via a PC using the free to use Thermon TraceView Network Explorer software or to integrate the controllers in a BMS or customized monitoring system.

The ECM-Ambient control modules are approved for use in both ordinary (nonclassified) and hazardous (classified) areas.

Features

  • Encapsulated electronics and control
  • One temperature control module for wide range of freeze protection applications
  • Energy saving accurate electronic temperature control action
  • Data highway communication capability
  • Control in degrees Centigrade or degrees Fahrenheit
  • Combines power junction box and control module in one unit
  • Single heating circuit switching or pilot control via a contactor
  • Ambient temperature sensor included
TraceNet ECM product variants
SKU P/N Item Type Voltage Cable profile Mounting type Switch type
TMN.A20.030 40-447.112.521 TraceNet ECM-A-12-P-WP-SP Ambient sensing 230 Vac BSX, RSX, KSX, HTSX, USX, VSX-HT, HPT, FP Wall Single pole

Other product variants of the ECM-Ambient range are available on request.

Certifications/Approvals

CE Ex
Certificate SIRA 12ATEX5239X
II 2(2) G Ex eb mb [ib] IICT4 Gb
II 2(2) D Ex tb IIIC T135°C IP66 Db

IEC IECEx
Certificate IECEx SIR 12.0103X
Ex eb mb [ib] IIC T4 Gb
Ex tb IIIC T135°C Db

Canadian Standards Association
Ordinary locations
Hazardous (classified) locations

Specifications

General

Manufacturer
Thermon
Unit of measurement
Piece

Ratings

Operating/control voltage
120 Vac +10%/-10% (50/60 Hz)
Operating/control voltage
230 Vac +10%/-10% (50/60 Hz)
Operating ambient range
-60°C to 55°C
Minimum ambient storage range
-74°C
Control switch type options
SPST and DPST
Switching current ratings SPST
30/30/20 A - 25°C, 40°C, 55°C
Switching current ratings DPST
28/23/17 A - 25°C, 40°C, 55°C
Alarm output current rating
2 A
Electrical connection
Terminal blocks
Adjustable temperature control range
0°C to 500°C
Measurement range
-60°C to 500°C
Measurement accuracy (ambient)
± 1°C (0°C to +55°C)
Measurement accuracy (ambient)
± 2°C (0°C to -60°C)
Temperature sensor(s)
100 Ohm three wire platinum RTD
RTD input circuitry
Intrinsically safe (Ex i)
Life expectancy
100,000 cycles
TraceNet ECM-Ambient

Request a quote

TraceNet ECM-Ambient

ring_volume +31 (0)183-201088 mail sales@tc-e.nl