TubeTrace with BSX

Features

  • 9, 15, 25 & 32 W/m @ 10°C
  • Tmax maintain 65°C
  • Cut-to-length
Request a quote Give us a call or send an email phonelink_ring +31 (0)183-201088 forward_to_inbox sales@tc-e.nl

Application

Thermon TubeTrace, with “cut-to-length” BSX self-regulating heat tracing, is designed to provide freeze protection or temperature maintenance from 5°C (40°F) to 65°C (150°F) for tubing where no “steam out” of the tubing is possible. BSX trace heating cable withstands temperature exposures of 185°F (85°C).

Thermon TubeTrace bundles with BSX heat trace cables are approved for use in ordinary (nonclassified) areas and hazardous (classified) areas.

Features

  • Pipe freeze protection and temperature maintenance up to 65°C (150°F)
  • BSX cable varies in response to the surrounding conditions along the entire length of a circuit
  • Lower risk of overheating the tube or product
  • Installed cost is lower because “cut-to-length” BSX cable makes end connections easy with minimal waste
  • BSX cable is approved for use in ordinary (non-classified) areas and hazardous (classified) areas
  • Polymer outer jacket (ATP or TPU available)

Certifications/Approvals

CE Ex
FM13 ATEX 0052 according to EU ATEX-directive 94/9/EC

IEC IECEx
FMG 13.0020

FM Approvals
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups B, C and D
Class II, Division 2, Groups F and G
Class III, Divisions 1 and 2
Class I, Zones 1 and 2, AEx e II

Underwriters Laboratories Inc.
Ordinary Locations
Hazardous (Classified) Locations

Canadian Standards Association
Ordinary Locations
Hazardous (Classified) Locations
Class I, Divisions 1 & 2, Groups A, B, C and D
Class II, Divisions 1 & 2, Groups E, F and G
Ex e II

Specifications

General

Manufacturer
Thermon
Unit of measurement
Meter

Ratings

Available watt densities (°C) 230 Vac
9, 15, 25, 32 W/m @ 10°C
Available watt densities (°C) 240 Vac
10, 16, 26, 33 W/m @ 10°C
Available watt densities (°F) 120 Vac
3, 5, 8, 10 W/ft @ 50°F
Supply voltages
110-120 or 208-277 Vac
Maximum maintain temperature
65°C (150°F)
Maximum continuous exposure temperature
Power-off 85°C (185°F)
T-rating
T6 85°C (185°F)
TubeTrace with BSX

Request a quote

TubeTrace with BSX