TubeTrace HTX2

Features

  • 15 W/m @ 10°C
  • Tmax maintain 5°C
  • Cut-to-length
Request a quote Give us a call or send an email phonelink_ring +31 (0)183-201088 forward_to_inbox sales@tc-e.nl

Application

Thermon TubeTrace HTX2 is a preengineered electric traced tubing bundle for steam sample lines and impulse lines to pressure transmitters. TubeTrace HTX2 will provide freeze protection by maintaining pipe temperatures of 5°C (40°F) of steam lines in ambient conditions down to -34°C (-30°F) with 40 kph (25 mph) wind conditions. These high temperature bundles are designed to withstand continuous 399°C (750°F) superheat steam temperatures and/or intermittent temperatures of 593°C (1100°F) for a duration of 2 minutes per cycle even when power is applied to the heat trace during ambient conditions of 5°C (40°F).

In the past, the only option for tubing subject to high temperature exposure was heat traced with series resistance mineral insulated (MIQ) heat trace. MIQ heaters are custom made to fit each application, so long lead times and specific field measurments are often required. TubeTrace HTX2 solves this with Thermon parallel resistance HPT heat trace isolated from direct contact with high temperature tubing.

Thermon TubeTrace HTX2 bundles are approved for use in ordinary (nonclassified) areas and hazardous (classified) areas.

Features

  • “Touch safe” jackets protect personnel
  • “Cut-to-length” for faster installation
  • Rated for intermittent exposure temperatures of 593°C (1100°F) for 2 minutes/2.5 hr cycle
  • Designed for ambient sensing control at 5°C (+40°F)
  • Freeze protect in ambient temperatures of -34°C (-30°F)
  • HPT cable is approved for use in ordinary (non-classified) areas and hazardous (classified) areas
  • Polymer outer jacket (ATP or TPU available)

Certifications/Approvals

FM Approvals
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups B, C and D
Class II, Division 2, Groups F and G*
Class III, Divisions 1 and 2
Division 1 Locations requires Heater Cable Option 8:
Class I, Division 1, Groups B, C and D
Class II, Division 1, Groups E, F and G

Underwriters Laboratories Inc.
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups B, C and D
Class II, Division 2, Groups E, F and G*
Class III, Divisions 1 and 2
Class I, Zone 1, AExe ll
Class I, Zone 2, AExe ll
Division 1 Locations requires Heater Cable Option 8:
Class I, Division 1, Groups B, C and D
Class II, Division 1, Groups E, F and G

Canadian Standards Association
Ordinary Locations
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups E, F and G
Class I, Division 1, Groups A, B, C and D
Class II, Division 1, Groups E, F and G
Ex e II

* CL. II, Div. 2 requires Thermon design review

Specifications

General

Manufacturer
Thermon
Unit of measurement
Meter

Ratings

Available watt densities (°C) 230 Vac
15 W/m @ 10°C
Supply voltages
120 to 240 Vac
Maintain temperature
5°C (40°F) freeze protection
Minimum design ambient
-34°C (-30°F)
Maximum continuous exposure temperature
399°C (750°F)
Intermittent service temperature
593°C (1100°F)
Minimum bend radius
SEI-HTX2: 305 mm (12") / MEI-HTX2: 406 mm (16")
TubeTrace HTX2